Marine CO2 Fire Suppression
Marine CO2 Fire Suppression System
-
Model
EHXT70 ENXT70 EHPXT70 Design Pressure(MPa)
15
Temperature(℃)
0~50 Cylinder(L)
70
Working Pressure(MPa)
5.7 Filling Rate(kg/L)
≤0.67 Pilot Gas Pressure(MPa)
6
Main Power(V)
220
Backup Power(V)
DC24 Application
Marine Inland watercraft Offshore Discharge
Time(min)
Total Flooding
<1 Local Application
>0.5 Activation Mode
Automatic/Manual/Emergency System
Independent or Combination Note
1. Carbon dioxide is a non-conductive, non-secondary pollution, no water loss, cheap and fire extinguishing agent. It can be used for extinguishing various flammable, inflammable liquids, solid surface fires, shallow deep fires and gas fires that can cut off the gas source before extinguishing. It is especially suitable for fire protection in precious reference rooms such as books, archives, computer rooms, aircraft garages, cabins, central control rooms and other places.
2. Because of the asphyxiation of carbon dioxide to human beings, carbon dioxide fire extinguishing equipment is not suitable for places where people are on duty.
Approvals
CCS
Offshore CO2 Fire Suppression System
-
Model
EHXT70 EHXT68
EHXT40 EHXT10 Design Pressure(MPa)
14.7
Temperature(℃)
0~49
Cylinder(L)
70
68 40 10 Delay Mode
Pneumatic Working Pressure(MPa)
5.7
Filling Rate(kg/L)
0.67
Pilot Gas Pressure(MPa)
6
Main Power(V)
220
Backup Power(V)
DC24
Application
Fishery
Discharge
Time(min)
Total Flooding <1
Local Application
>0.5 Activation Mode
Automatic/Manual/Emergency
Note
1. Carbon dioxide is a non-conductive, non-secondary pollution, no water loss, cheap and fire extinguishing agent. It can be used for extinguishing various flammable, inflammable liquids, solid surface fires, shallow deep fires and gas fires that can cut off the gas source before extinguishing. It is especially suitable for fire protection in precious reference rooms such as books, archives, computer rooms, aircraft garages, cabins, central control rooms and other places.
2. Because of the asphyxiation of carbon dioxide to human beings, carbon dioxide fire extinguishing equipment is not suitable for places where people are on duty.
Approvals
ZY
Marine HFS Fire Suppression
HFC-227ea 4.2MPa Fire Suppression System
-
Model
QMQ4.2/70N
QMQ4.2/90N
QMQ4.2/120N
QMQ4.2/150N150
QMQ4.2/180N Design Pressure
(MPa)
5.6
Temperature(℃)
0 ~ 50 Cylinder Size
70 90 120 150 180 Working Pressure
(MPa)
4.2
Filling Rate(kg/L)
0.95
Pilot Gas
N2 Pilot Gas Pressure
(MPa)
6 Main Power(V)
AC220
Backup Power(V)
DC24 Discharge Time
(min)
≤10
Activation Mode
Automatic/Manual/Emergency
System
Independent or Combination Note
High fire-extinguishing efficiency、nonpollution, substitute product for Halon Approvals
CCCF